NOPS
NOPSEMA
Date not published
F233-20
6 pages
PDF
On 5 September 2022, Woodside Energy Ltd reported a minor loss of primary containment (LOPC) from a gas injection line in the turret of the Vincent offshore facility (WA) during routine operator rounds. The incident involved icing detected on a fuel injection line with no gas…
-
NOPS
NOPSEMA
Date not published
F233-19
4 pages
PDF
Woodside Energy Ltd reported a notifiable incident (NTF11753) on 5 September 2022 involving the CWLH OKHA FPSO facility off Western Australia. During routine inspections of lifting operations, two brass bushes in the aft crane's slew encoder drive gear were found displaced by 30…
-
NOPS
NOPSEMA
Date not published
F233-18
4 pages
PDF
Woodside Energy Ltd notified NOPSEMA of a dangerous occurrence at the Vincent offshore facility on 31 August 2022 involving failure of a locking arm on a turret free drop unit during routine maintenance pressure testing. One of eight locking arms failed to meet performance…
-
NOPS
NOPSEMA
Date not published
F233-17
5 pages
PDF
Woodside Energy Global reported a notifiable incident (NTF11740) at the Pyrenees facility on 30 August 2022 involving a vacuum release line at the 3S cargo oil pump discovered during planned radiography inspections with wall thickness of 0.65mm, below the minimal allowable wall…
-
NOPS
NOPSEMA
Date not published
F233-16
4 pages
PDF
Woodside Energy Ltd reported a dangerous occurrence on the CWLH OKHA FPSO in Western Australia on 26 August 2022, involving failure of a safety-critical crane component. The aft crane slew encoder developed an 8-degree offset that compromised the collision avoidance system…
-
NOPS
NOPSEMA
Date not published
F233-15
4 pages
PDF
Woodside Energy Global reported a dangerous occurrence at the Pyrenees facility in Western Australia on 18 August 2022. During routine piping inspection, corrosion and wall loss were detected on two spots of the #1 boiler fuel gas supply line, with thickness measurements falling…
-
NOPS
NOPSEMA
Date not published
F233-14
4 pages
PDF
Woodside Energy Ltd notified NOPSEMA of a dangerous occurrence on 17 August 2022 involving the CWLH OKHA FPSO in Western Australian waters. The lift gas compressor #1 emergency anti-surge station had one of two inputs non-functional due to an incorrect pressure transmitter…
-
NOPS
NOPSEMA
Date not published
F233-13
3 pages
PDF
Woodside Energy Ltd reported a notifiable incident (NTF11662) involving the CWLH OKHA FPSO facility offshore Western Australia on 23 July 2022, in which a forward starboard bow fire monitor failed to operate remotely during routine yearly testing. The equipment functioned…
-
NOPS
NOPSEMA
Date not published
F233-12
4 pages
PDF
Woodside Energy Ltd notified NOPSEMA of a dangerous occurrence at the Vincent offshore facility in Western Australia on 24 July 2022, involving loss of hydraulic power to crane #6 due to Human Machine Interface (HMI) failure during supply vessel offloading operations. No load…
-
NOPS
NOPSEMA
Date not published
F233-11
3 pages
PDF
On 24 July 2022, Woodside Energy Global Pty Ltd notified NOPSEMA of a dangerous occurrence at the Pyrenees offshore facility in Western Australia involving multiple structural failures in bund walls and penetrations. During a detailed inspection campaign that included mechanical…
-
NOPS
NOPSEMA
Date not published
F233-10
3 pages
PDF
NOPSEMA released a notifiable incident report (NTF11653) documenting an inadvertent activation of the Fire and Gas detection system at Woodside Energy's Vincent facility on 21 July 2022. The unplanned general alarm occurred during testing of an upgraded Consilium fire detection…
-
NOPS
NOPSEMA
Date not published
F233-09
3 pages
PDF
Woodside Energy Ltd notified NOPSEMA of a dangerous occurrence at the Vincent facility on 18 July 2022 involving failure of a process control module (PCM) during shunt trip testing. The electrical failure occurred when device 64-XS-4055 failed to trip non-Ex loads in the…
-
NOPS
NOPSEMA
Date not published
F233-08
5 pages
PDF
Woodside Energy Ltd reported a notifiable incident (NTF11645) on 14 July 2022 at the Vincent offshore facility in Western Australia involving two safety-critical valves that failed to meet performance standards during annual emergency shutdown (ESD) testing. One valve (Inlet…
-
NOPS
NOPSEMA
Date not published
F233-07
5 pages
PDF
Woodside Energy Ltd notified NOPSEMA of a dangerous occurrence on 14 July 2022 involving significant corrosion discovered in a high-pressure gas compressor on the Vincent facility in Western Australia. During routine inspection of a 50mm suction line, corrosion was identified at…
-
NOPS
NOPSEMA
Date not published
F233-06
5 pages
PDF
Woodside Energy Ltd reported a notifiable incident (NTF11640) on 12 July 2022 involving damage to the main hoist rope on the midships crane of the CWLH OKHA FPSO in Western Australian waters. During a routine weekly inspection, the rope showed apparent outer layer damage…
-
NOPS
NOPSEMA
Date not published
F233-05
3 pages
PDF
Woodside Energy Ltd notified NOPSEMA of a non-work-related medical incident aboard the CWLH OKHA FPSO on 12 July 2022. A crew member presented with a headache, disorientation, and memory loss and was medevaced to Karratha Health Campus on advice from the facility's medical…
-
NOPS
NOPSEMA
Date not published
F233-04
4 pages
PDF
Woodside Energy Ltd notified NOPSEMA of a notifiable incident (NTF11628) at the Vincent offshore facility on 10 July 2022, when a ultraviolet flame detector in the engine room unexpectedly activated, triggering a general alarm and personnel muster. No fire, damage, or…
-
NOPS
NOPSEMA
Date not published
F233-03
4 pages
PDF
Woodside Energy Ltd notified NOPSEMA on 10 July 2022 of a dangerous occurrence at the Vincent offshore facility in Western Australia involving a failed quick closing valve in the engine room. During routine six-monthly function testing, a pneumatic ram on the quick closing valve…
-
NOPS
NOPSEMA
Date not published
F233-02
4 pages
PDF
Woodside Energy Global notified NOPSEMA of a dangerous occurrence at its Pyrenees offshore facility in Western Australia on 1 July 2022, involving a failed level switch on the main pressure-vacuum (PV) breaker during routine function testing on 30 June 2022. The switch, designed…
-
NOPS
NOPSEMA
Date not published
F233-01
4 pages
PDF
Woodside Energy Global reported a notifiable incident (NTF11607) at the Pyrenees facility in Western Australia on 1 July 2022 involving integrity failure of a chemical bund. A 50mm pipe stub that penetrated the bund floor corroded and disconnected, compromising the bund's…